Eaton 9355 UPS (10/15 kVA) User’s Guide 164201594—Rev H0 43
Figure 26. Version 1 Internal Cover
Internal
Cover
7. Punch holes for the conduit (AC input, UPS output, load connection, and maintenance bypass contact
wires) using a Greenlee punch or similar device.
8. Verify that the bypass breaker is in the OFF position (see Figure 27).
9. Mount the bypass cabinet to the wall and install the conduit.
Figure 27. Version 1 Bypass Breaker
10. Verify that the UPS battery circuit breaker is in the OFF position (see Figure 28).
11. Remove the UPS wiring access cover and one of the conduit landing plates and retain.