Eaton® 9390 (100–160 kVA) UPS Installation and Operation Manual 164201604—Rev F 118
3. To restart the UPS after using the REPO pushbutton, follow the procedure in
9.2.1 Starting the Parallel System in Normal Mode or 9.2.2 Starting the Parallel System in Bypass Mode.
NNOOTTEE Follow Lockout/Tagout (LOTO) procedures for your location. The key should not be
stored in the switch. DO NOT insert the key until the fault is resolved.
FFiigguurree 7744.. RREEPPOO OOppeerraattiioonn
Deactivated
Unlock pushbutton to release
Activated
Pushbutton locked into place
UPS Operating Instructions
For Internal Use Only