1.The UPS equipment operating environment must meet the weight requirements shown in
Table A and the size requirements shown on Figure 84
.
2.The UPS cabinet is palleted separately for shipping.
3.Do not tilt cabinets more than
10° during handling.
4.Dimensions are in millimeters (inches).
5.The cabinet can be installed inline‐up‐and‐matchorstandaloneconfigurations.
Table A. UPS Cabinet Weight
Model
Voltage
Weight
kg (lb)
Input Output Shipping Installed Point Loading
Eaton 9390-120/100
208V/220V 208V/220V 531 (1170) 504 (1110) 6 at 84 (185)
380V/400V/
415V/480V
380V/400V/
415V/480V
467 (1030) 440 (970) 6 at 73 (162)
Eaton 9390-120/120
208V/220V 208V/220V 531 (1170) 504 (1110) 6 at 84 (185)
380V/400V/
415V/480V
380V/400V/
415V/480V
467 (1030) 440 (970) 6 at 73 (162)
Eaton 9390-160/100
208V/220V 208V/220V
581 (1280) 553 (1220) 6 at 92 (204)
380V/400V/
415V/480V
380V/400V/
415V/480V
Eaton 9390-160/120
208V/220V 208V/220V
581 (1280) 553 (1220) 6 at 92 (204)
380V/400V/
415V/480V
380V/400V/
415V/480V
Eaton 9390-160/160
208V/220V 208V/220V
581 (1280) 553 (1220) 6 at 92 (204)
380V/400V/
415V/480V
380V/400V/
415V/480V
6.The clearances required around the UPS cabinet are shown in Table B.
Table B. UPS Cabinet Clearances
From Top of Cabinet Minimum clearance over the UPS cabinet is
457.2 mm (18 in.) for ventilation
From Front of Cabinet 914.4 mm (36 inches) working space
From Back of Cabinet None required
From Right Side of Cabinet None required
From Left Side of Cabinet None required