Eaton® 9390 (100–160 kVA) UPS Installation and Operation Manual 164201604—Rev F 14
CChhaapptteerr 44 IInnssttaalllliinngg tthhee UUPPSS SSyysstteemm
This chapter describes the UPS system installation for single modules and multi-modules, including: unloading
the cabinets, UPS internal and external wiring, and interface connections.
44..11 PPrreelliimmiinnaarryy IInnssttaallllaattiioonn IInnffoorrmmaattiioonn
Installation should be performed only by qualified personnel.
Refer to the following while installing the UPS system:
• Chapter 15 Installation Information contains installation drawings and additional installation notes.
• Dimensions are in millimeters and inches.
• Do not tilt the UPS cabinets more than ±10° from vertical or the cabinet may tip over.
• Remove the conduit landing plates to add conduit landing holes as required. Plate material is 16 gauge
steel (1.5 mm/0.06" thick).
• The UPS cabinets must be installed on a level floor suitable for computer or electronic equipment.
• If perforated floor tiles are required for ventilation, place them in front of the UPS. See Table A for
equipment weight and point loading.
• Details about control wiring are provided in each procedure for connecting options and features. Figure 86
Table R through Table X identify the control wiring terminations.
44..22 UUnnllooaaddiinngg tthhee UUPPSS CCaabbiinneett ffrroomm tthhee PPaalllleett aanndd MMeecchhaanniiccaall IInnssttaallllaattiioonn
NNOOTTEE 11 When a line-up-and-match UPS system is ordered together with battery cabinets, the
first battery cabinet is supplied with two cosmetic covers. The UPS cabinet, additional
battery cabinets, and other ancillary cabinets are supplied without cosmetic covers.
NNOOTTEE 22 When a UPS system is ordered together with battery cabinets for standalone
installation, the first battery cabinet is supplied with two cosmetic covers. Additional
battery cabinets are supplied without cosmetic covers. Cosmetic covers must be
ordered for the UPS cabinet and/or other ancillary cabinets.
• The UPS cabinet is heavy. See Table A of Figure 80 for weight of cabinets. If unloading instructions are not
closely followed, the cabinet may cause serious injury.
• Do not tilt cabinets more than 10° from vertical.
Each UPS cabinet is bolted to a wooden pallet supported by wood skids.
To remove the pallet:
1. If not already in position, use a forklift or pallet jack to move the cabinet to the installation area, or as close
as possible, before unloading from the pallet. Insert the forklift or pallet jack forks between the skids on
the bottom of the unit.