173 Eaton® 9390 (100–160 kVA) UPS Installation and Operation Manual 164201604—Rev F
FFiigguurree 8866.. 116644220011660044--88 IInntteerrffaaccee WWiirriinngg IInnssttaallllaattiioonn NNootteess aanndd TTeerrmmiinnaall LLooccaattiioonnss
1 of 15
INTERFACE WIRING INSTALLATION
NOTES AND TERMINAL LOCATIONS
032406 B
DESCRIPTION:
DATE:
: T E E H S : O N G N I W A R D
REVISION:
164201604-8
1.Use Class 1 wiring methods (as defined by the NEC) for interface wiring up to 30V. The
wire should be rated at 24V, 1A minimum.
2.Use Class 2 wiring methods (as defined by the NEC) for interface wiring from 30 to 600V.
3.When installing external interface wiring (for example, building alarm, relay output, battery
breaker trip, and X-Slot) to the UPS interface terminals, conduit must be installed between
each device and the UPS cabinet. Install the interface wiring in separate conduit from the
power wiring.
4.When installing internal interface wiring to X-Slot terminals, route the wiring through the
internal opening in the X-Slot communication bay.
5.All building alarm inputs require an isolated normallyopen contact or switch (rated at
24 Vdc, 20 mA minimum) connected between the alarm input and common terminal
as shown. Building alarm inputs can be programmed for use with either normally–open or
normally–closed contacts. All control wiring and relay and switch contacts are
customersupplied. Use twistedpair wires for each alarm input and common.
6.The building alarms can be programmed to display the alarm functional name.
7.See Tables R through X and Chapter 4
, Chapter 5 , and Chapter 6 for customer interface wiring.
8.LAN and telephone drops for use with X-Slot connectivity cards must be provided by
facility planners or the customer.
Table R. TB1 and TB2 Interface Connections
Terminal TB1 Name Description
1
Remote EPO NC
Normallyclosed dry contacts used to activate EPO
of UPS from a remote switch
2 Remote EPO Common
3 Remote EPO NO
Normallyopen dry contacts used to activate EPO of
UPS from a remote switch
4 Remote EPO Common
5 Battery Breaker Aux
Contacts used to indicate whether UPS battery
breaker or disconnect is open or closed.
6
Battery Breaker Aux
Return
7 Battery UVR (+)
Contacts used to open battery breaker or
disconnect.
8 Battery UVR (-)
9 Building Alarm 1
Programmable UPS alarm. Activated by a remote
dry contact closure.
10 Building Alarm 1 Return
Terminal TB2 Name Description
1 Building Alarm 2
Programmable UPS alarm. Activated by a remote
dry contact closure. Also used for backup control
(pull chain) for parallel operation.
2 Building Alarm 2 Return
3 On Bypass Return
Normallyopen contact closes when UPS is on
bypass. Also used for backup control (pull chain)
for parallel operation.
4 On Bypass NO
5 Alarm Relay NC
General purpose normallyclosed relay contact.
6 Alarm Relay Common
7 Alarm Relay NO
General purpose normallyopen relay contact.
8 Alarm Relay Common
9 On Inverter NC
Normallyclosed contact opens when output
contactor closes.
10 On Inverter Return
Installation Information