The components inside the UPS cabinet are secured to a sturdy metal frame that is supported by the UPS
magnetics. This design allows authorized service personnel to remove repairable components with very little
disassembly. All repairable parts and assemblies are located in the front of the UPS, allowing all routine
maintenance and servicing to be performed with front panel access.
Schedule periodic performance checks of your UPS system to keep it running properly. Regular routine checks
of operation and system parameters will enable your system to function efficiently for many trouble –free
years.
1133..11 IImmppoorrttaanntt SSaaffeettyy IInnssttrruuccttiioonnss
Remember that your UPS system is designed to supply power EEVVEENN WWHHEENN DDIISSCCOONNNNEECCTTEEDD FFRROOMM TTHHEE
UUTTIILLIITTYY PPOOWWEERR. The UPS cabinet interiors are unsafe until the DC power source is disconnected and the
electrolytic capacitors are discharged. After disconnecting the utility power and the DC power, authorized
service personnel should wait at least five minutes for capacitor bleedoff before attempting internal access to
the UPS module.
This UPS contains LETHAL VOLTAGES. All repairs and service should be performed by AUTHORIZED SERVICE
PERSONNEL ONLY. There are NO USER SERVICEABLE PARTS inside the UPS.
• Servicing and maintenance should be performed by qualified service personnel only.
• LETHAL VOLTAGE PRESENT. DO NOT operate with the cabinet doors open or safety shields removed.
Do not make any assumptions about the electrical state of any cabinet in the UPS system.
• See Chapter 2 Safety Warnings.
Since each battery string is an energy source in itself, opening the Battery Circuit Breaker does not de–energize
the voltage within the battery string. DDOO NNOOTT AATTTTEEMMPPTT TTOO AACCCCEESSSS AANNYY IINNTTEERRNNAALL AARREEAA OOFF TTHHEE
BBAATTTTEERRYY SSTTRRIINNGG YYOOUURRSSEELLFF.. VVOOLLTTAAGGEESS AARREE AALLWWAAYYSS PPRREESSEENNTT IINN TTHHEE BBAATTTTEERRYY SSTTRRIINNGG..
If the string requires service, refer to the battery manufacturer's operating manual for instructions on battery
maintenance, or contact your Eaton service representative.
Maintaining the UPS System