Eaton® 9390 (100–160 kVA) UPS Installation and Operation Manual 164201604—Rev F 62
Press the CCHHAANNGGEE pushbutton on the Current kW Demand Log Setup Menu bar to display the Current kW
Demand Log Setup screen 2.
The Current kW Demand Log Setup screen can be used to set up or change the time interval and maximum
level log settings. Figure 32 shows the Current kW Demand Log Setup screen 2.
Use the
USING THE CONTROL PANEL
Eaton 9390 UPS (20–80 kVA) and 9390IT (20-40 kVA) Installation and Operation Manual S 164201603 Rev 4
8-4
8.2.2 Event Screens
Press the EVENTS pushbutton on the main menu bar or History Menu bar to display a
listing of all system events that are currently active. The most recent event is listed
first. As events clear, they are removed from the Active System Events listing.
Figure 8‐4 shows the Active Events screen.
To scroll through the events, press the
or pushbuttons on the menu bar.
ACTIVE EVENTS
HISTORY
ALARM: INPUT AC UNDERVOLTAGE
ALARM: BYPASS AC UNDER VOLTAGE
NOTICE: BATTERY VOLTAGE LOW
NOTICE: NO SYNC ON
NOTICE: BYPASS NOT AVAILABLE
NOTICE: CONFIGURATION ERROR
Figure 8‐4. Active Events Screen
or
USING THE CONTROL PANEL
Eaton 9390 UPS (20–80 kVA) and 9390IT (20-40 kVA) Installation and Operation Manual S 164201603 Rev 4
8-4
8.2.2 Event Screens
Press the EVENTS pushbutton on the main menu bar or History Menu bar to display a
listing of all system events that are currently active. The most recent event is listed
first. As events clear, they are removed from the Active System Events listing.
Figure 8‐4 shows the Active Events screen.
To scroll through the events, press the
or pushbuttons on the menu bar.
ACTIVE EVENTS
HISTORY
ALARM: INPUT AC UNDERVOLTAGE
ALARM: BYPASS AC UNDER VOLTAGE
NOTICE: BATTERY VOLTAGE LOW
NOTICE: NO SYNC ON
NOTICE: BYPASS NOT AVAILABLE
NOTICE: CONFIGURATION ERROR
Figure 8‐4. Active Events Screen
pushbuttons to highlight the setup function screen desired, then press the SSEELLEECCTT
pushbutton to display the function screen.
To return to the Current kW Demand Log Setup screen 1, press the
USING THE CONTROL PANEL
Eaton 9390 UPS (20–80 kVA) and 9390IT (20-40 kVA) Installation and Operation Manual S 164201603 Rev 4
8-3
8.2 Using the Main Menu
The UPS main menu bar allows you to display data in the information area to help you
monitor and control UPS operation. The following menus and options are available:
Menu Option Description
EVENTS Displays the list of Active System Events and a historical log of system events.
METERS Displays performance meters for the system or critical load.
CONTROLS Displays the System Controls screen.
SETUP Allows you to set the display contrast, set the date and time for the time stamp,
configure the UPS serial communication ports, and view the firmware version numbers.
LOAD OFF De-energizes the critical load and powers down the UPS.
Returns to Main Menu and Mimic screen from the Events, Meters, Controls, or Setup
screens. Returns to the main System Setup Level screen from a setup submenu.
8.2.1 Mimic Screen
Figure 8‐3 shows the Main Menu and Mimic screen. To select the Mimic screen from
the Events, Meters, Controls, or Setup screens, press the
pushbutton on the
current menu bar.
The Mimic screen shows the internal components of the UPS cabinet and a real‐time
graphical representation of the operating status of the system.
TIME: 11 : 35 : 43 DATE: 02 / 25 / 2004
CONTROLS LOAD OFF
METERSEVENTS SETUP
OUTPUT
BATT
UPS
INPUT
STSW
BYPASS
Figure 8‐3. Main Menu and Mimic Screen (Normal Mode)
pushbutton on the menu bar.
FFiigguurree 3322.. CCuurrrreenntt kkWW DDeemmaanndd LLoogg SSeettuupp SSccrreeeenn 22
TIME INTERVAL MONITORED
CURRENT KW DEMAND LOG SETUP
SELECT
MAXIMUM LEVEL (KW)
Using the Control Panel