125 Eaton® 9390 (100–160 kVA) UPS Installation and Operation Manual 164201604—Rev F
TTaabbllee 66.. AAllaarrmmss ((CCoonnttiinnuueedd))
MMeessssaaggee
HHoorrnn PPhhoonnee
RReellaayy LLoogg**
IInnddiiccaattiioonn
Check Fan OK Off No
1
HA Condition Cleared
Check Input Switchgear
1 1 1
HA Service Required
Check Input Switchgear OK Off No
1
HA Condition Cleared
Check Inv Temperature Sensor
1
No
1
HA Service Required
Check Inv Temperature Sensor OK Off
No
1
HA
Condition Cleared
Check Inverter
1 1 1
HA Service Required
Check Logic Power Supply
1
No
1
HA Service Required
Check Logic Power Supply OK Off No
1
HA Condition Cleared
Check Output Switchgear
1
No
1
HA Service Required
Check Output Switchgear OK Off No
1
HA Condition Cleared
Check Power Supply
1 1 1
HA Service Required
Check Power Supply OK Off No
1
HA Condition Cleared
Check Precharge
1
No
1
HA Service Required
Check Precharge OK Off No
1
HA Condition Cleared
Check Rect Temperature Sensor
1
No
1
HA Service Required
Check Rect Temperature Sensor OK Off No
1
HA Condition Cleared
Check Rectifier
1 1 1
HA Service Required
Check Static Switch
1 1 1
HA Service Required
Check Static Switch OK Off No
1
HA Condition Cleared
Close Battery Switchgear
1 1 1
HA User Action Required
Close Battery Switchgear OK Off No
1
HA Condition Cleared
Configuration Error
1
No
1
HA Service Required
Configuration Error OK Off No
1
HA Condition Cleared
External Comm Failure
1
No
1
HA Service Required
External Comm Failure OK Off
No
1
HA
Condition Cleared
Internal Comm Failure
1
No
1
HA Service Required
Internal Comm Failure OK Off No
1
HA Condition Cleared
Invalid Board ID
1
No
1
HA
Service Required
Invalid Board ID OK Off No
1
HA Condition Cleared
Inverter L1 Current Limit
1
No
1
HA Service Required
Inverter L2 Current Limit
1
No
1
HA
Service Required
Inverter L3 Current Limit
1
No
1
HA Service Required