Eaton® 9390 (100–160 kVA) UPS Installation and Operation Manual 164201604—Rev F 124
CChhaapptteerr 1111 RReessppoonnddiinngg ttoo SSyysstteemm EEvveennttss
1111..11 GGeenneerraall
When the UPS system is running in Normal mode, it continually monitors itself and the incoming utility power.
In Battery or Bypass modes, the UPS may issue alarms to let you know exactly what event caused the change
from Normal mode. System events on the UPS can be indicated by horns, lights, messages, or all three.
Select EEvveennttss from the menu bar on the Main Menu screen to look at the Active System Events screen. This
screen shows any currently active alarms, notices, or commands. For more information on using the Events
screen, see 8.2.2 Event Screens.
1111..22 SSyysstteemm EEvveenntt HHoorrnnss
The system event horn beeps to alert an operator that an event needing attention is taking place. Horn 1 cycles
at a one-second rate.
1111..33 SSyysstteemm EEvveenntt IInnddiiccaattoorrss
The status indicators on the UPS control panel work in conjunction with the event horn to let you know when
the UPS system is operating in any mode other than Normal. Only the Normal indicator is visible during normal
UPS system operation. The other indicators illuminate to indicate alarms or events. When an alarm occurs, you
should first check these indicators to see what type of event has taken place. For descriptions of the status
indicators, see 8.5 Reading the Status Indicators.
1111..44 SSyysstteemm EEvveenntt MMeessssaaggeess
When a system event occurs, a message appears on the LCD in the UPS status area. This message is also
written to the Active Events log and may be added to the Events History log. The messages are divided into
four categories: alarms, notices, status, and commands. The following tables contain the events displayed on
the Events screen of the control panel.
TTaabbllee 66.. AAllaarrmmss
MMeessssaaggee
HHoorrnn PPhhoonnee
RReellaayy LLoogg**
IInnddiiccaattiioonn
Battery Totally Discharged
1
No
1
HA Shutdown Imminent
Battery Totally Discharged OK Off No
1
HA Condition Cleared
Building Alarm 1
1
No
1
HA User Action Required
Building Alarm 1 OK Off No
1
HA Condition Cleared
Building Alarm 2
1
No
1
HA User Action Required
Building Alarm 2 OK Off
No
1
HA
Condition Cleared
Check Bypass
1 1 1
HA
Service Required
Check Bypass OK Off No
1
HA Condition Cleared
Check Bypass Switchgear
1
No
1
HA Service Required
Check Bypass Switchgear OK Off No
1
HA Condition Cleared
Check Charger
1 1 1
HA Service Required
Check Charger OK Off No
1
HA Condition Cleared
Check Fan
1
No
1
HA Service Required