13 Eaton® 9390 (100–160 kVA) UPS Installation and Operation Manual 164201604—Rev F
The UPS cabinet is heavy (see Table A of Figure 80). If unpacking instructions are not closely followed, the
cabinet may tip and cause serious injury.
• Do not install a damaged cabinet. Report any damage to the carrier and contact your Eaton service
representative immediately.
• Do not tilt the UPS cabinet more than 10° from vertical or the cabinet may tip over.
To unpack the cabinet:
1. Carefully inspect the outer packaging for evidence of damage during transit.
2. Use a forklift or pallet jack to move the packaged cabinet to the installation site, or as close as possible,
before unpacking. Insert the forklift or pallet jack forks between the pallet supports on the bottom of the
unit.
NNOOTTEE Verify that the forklift or pallet jack is rated to handle the weight of the cabinet (see Table
A of Figure 80 for cabinet weight).
3. Set the pallet on a firm, level surface, allowing a minimum clearance of 3m (10 ft) on each side for
removing the cabinet from the pallet.
NNOOTTEE The UPS cabinet is shipped with a debris shield covering the ventilation grill on top of
the unit. Do not remove the debris shield until installation is complete.
4. Remove the protective covering from the cabinet.
5. Remove the packing material, and discard or recycle in a responsible manner.
6. Inspect the contents for any evidence of physical damage, and compare each item with the Bill of Lading.
If damage has occurred or shortages are evident, contact your Eaton service representative immediately to
determine the extent of the damage and its impact upon further installation.
NNOOTTEE While waiting for installation, protect the unpacked cabinet from moisture, dust, and
other harmful contaminants. Failure to store and protect the UPS properly may void your
warranty.
UPS Installation Plan and Unpacking