PHYSICAL FEATURES AND REQUIREMENTS
011509 C
164201604-2
DESCRIPTION:
DATE:
: T E E H S : O N G N I W A R D
REVISION:
7.The basic environmental requirements for operation of the UPS system are:
Ambient Temperature Range:0-40°C (32-104°F)
Recommended Operating Range:20-25°C (68-77°F)
Maximum Relative Humidity:95%, noncondensing
The UPS ventilation requirements are shown in Table C.
Table C. Air Conditioning or Ventilation Requirements During Full Load Operation
Ratings
Voltage
Heat Rejection
BTU/hr
1000/hr (kg‐cal/hr)
Input Output
100 kVA 208/220 208/220 29.6 (7.45)
100 kVA 380/400/415/480 380/400/415/480 27.4 (6.90)
120 kVA 208/220 208/220 35.5 (8.94)
120 kVA 380/400/415/480 380/400/415/480 32.8 (8.28)
160 kVA 208/220 208/220 47.3 (11.9)
160 kVA 380/400/415/480 380/400/415/480 43.8 (11.0)
Ventilation required for cooling air exhaust: approximately 944 liter/sec (2000 cfm).