Eaton® 9390 (100–160 kVA) UPS Installation and Operation Manual 164201604—Rev F 138
CChhaapptteerr 1144 PPrroodduucctt SSppeecciiffiiccaattiioonnss
The following sections detail the input, output, environmental, and battery specifications for the UPS.
1144..11 MMooddeell NNuummbbeerrss
The UPS systems are housed in free–standing cabinets with safety shields behind the doors. The UPS systems
are available in 50/60 Hz with various output power ratings.
MMooddeellss
PPoowweerr RRaattiinngg FFrreeqquueennccyy
Eaton 9390-120/100 100 kVA 50/60 Hz
Eaton 9390-120/120 120 kVA 50/60 Hz
Eaton 9390-160/100 100 kVA 50/60 Hz
Eaton 9390-160/120 120 kVA 50/60 Hz
Eaton 9390-160/160 160 kVA 50/60 Hz
The following sections detail the input, output, environmental, and battery specifications for the UPS.
1144..22 SSiinnggllee MMoodduullee SSppeecciiffiiccaattiioonnss
1144..22..11 UUPPSS SSyysstteemm IInnppuutt
OOppeerraattiinngg IInnppuutt VVoollttaaggee
((NNoommiinnaall ++1100// 1155%%))
208 Vac for operation from 177 Vac to 229 Vac
220 Vac for operation from 187 Vac to 242 Vac
380 Vac for operation from 323 Vac to 418 Vac
400 Vac for operation from 340 Vac to 440 Vac
415 Vac for operation from 353 Vac to 457 Vac
480 Vac for operation from 408 Vac to 528 Vac
OOppeerraattiinngg IInnppuutt FFrreeqquueennccyy RRaannggee ±5 Hz
OOppeerraattiinngg IInnppuutt CCuurrrreenntt
See Table E through Table G of Figure 82 to Figure 84.
Reduced for Generator
Adjustable
IInnppuutt CCuurrrreenntt HHaarrmmoonniicc CCoonntteenntt 5% THD at full load
PPoowweerr FFaaccttoorr Minimum 0.99
LLiinnee SSuurrggeess 6 kV OC, 3 kA SC per ANSI 62.41 and IEC 801 4
BBaatttteerryy VVoollttaaggee
384 Vdc (208V/220V units only)
432 Vdc
480 Vdc