175 Eaton® 9390 (100–160 kVA) UPS Installation and Operation Manual 164201604—Rev F
FFiigguurree 8866.. 116644220011660044--88 IInntteerrffaaccee WWiirriinngg IInnssttaallllaattiioonn NNootteess aanndd TTeerrmmiinnaall LLooccaattiioonnss ((CCoonnttiinnuueedd))
NOTE:1. All building alarm inputs require an isolated normallyopen or
normallyclosed contact or switch (rated at 24 Vdc, 20 mA minimum)
connected between the alarm input and common terminal as shown. Building
alarm inputs can be programmed for use with either normallyopen or
normallyclosed contacts. All control wiring and relay and switch contacts are
customersupplied.
2. The building alarms can be programmed to display the alarm functional
name.
3. A jumper wire must be connected between pins 1 and 2 on TB1, if the
normallyclosed EPO contact is not used.
032406 B
164201604-8
DESCRIPTION:
DATE:
: T E E H S : O N G N I W A R D
REVISION:
INTERFACE WIRING INSTALLATION
NOTES AND TERMINAL LOCATIONS
INTERFACE TERMINALS
3 of 15
BUILDING ALARM 2 RETURN
BUILDING ALARM 1
1
10
1
10
TB1
TB2
BUILDING ALARM 1 RETURN
BUILDING ALARM 2
ALARM RELAY NC
ALARM RELAY COMMON
ALARM RELAY NO
REMOTE EPO NO
REMOTE EPO NC
EPO COMMON
BATTERY BREAKER AUX
BATTERY BREAKER AUX RETURN
BATTERY UVR (+)
BATTERY UVR (-)
UPS
ON BYPASS NO
ON BYPASS RETURN
ON INVERTER NC
ON INVERTER RETURN
EPO COMMON
ALARM RELAY COMMON
JUMPER REQUIRED
IF NOT USED