179 Eaton® 9390 (100–160 kVA) UPS Installation and Operation Manual 164201604—Rev F
FFiigguurree 8866.. 116644220011660044--88 IInntteerrffaaccee WWiirriinngg IInnssttaallllaattiioonn NNootteess aanndd TTeerrmmiinnaall LLooccaattiioonnss ((CCoonnttiinnuueedd))
032406 B
164201604-8
DESCRIPTION:
DATE:
: T E E H S : O N G N I W A R D
REVISION:
INTERFACE WIRING INSTALLATION
NOTES AND TERMINAL LOCATIONS
7 of 15
14.Wire the maintenance bypass auxiliary contacts as applicable. See Table V.
Table V. Typical Maintenance Bypass Panel Auxiliary Contact Control Wiring
TB2
34
MAINTENANCE BYPASS PANEL
(PROVIDED BY OTHERS)
UPS
NOTE: REFER TO THE INSTRUCTIONS
PROVIDED WITH THE MAINTENANCE
BYPASS PANEL FOR WIRING INSTRUCTIONS.
MBP
AUX 1
N. O.
COMMON
AUX CONTACT RATING
Refer to the instructions provided with the maintenance bypass panel
for auxiliary contact ratings.
Minimum Wire Size: 22 AWG
Installation Information