Eaton® 9390 (100–160 kVA) UPS Installation and Operation Manual 164201604—Rev F 182
FFiigguurree 8866.. 116644220011660044--88 IInntteerrffaaccee WWiirriinngg IInnssttaallllaattiioonn NNootteess aanndd TTeerrmmiinnaall LLooccaattiioonnss ((CCoonnttiinnuueedd))
091505 A
164201604-8
DESCRIPTION:
DATE:
: T E E H S : O N G N I W A R D
REVISION:
INTERFACE WIRING INSTALLATION
NOTES AND TERMINAL LOCATIONS
NOTE:This drawing is for parallel wiring purposes and is not a floor layout plan.
UPMs can be placed in any physical order.
PARALLEL SYSTEM CAN AND BACKUP CONTROL (PULL CHAIN)
UPM
1
UPM
2
UPM
3
UPM
4
CAN
(IF INSTALLED)
(IF INSTALLED)
PULL CHAIN
PARALLEL SYSTEM CAN WIRING
10 of 15
TWISTED PAIR
TWISTED PAIR
TWISTED PAIR
UPM 1
CAN CARD J3
UPM 2
CAN CARD J3
UPM 3
CAN CARD J3
(IF INSTALLED)
UPM 4
CAN CARD J3
(IF INSTALLED)
CAN Wiring Terminations
From UPM 1 CAN Card To UPM 2 CAN Card
To UPM 3 CAN Card
(If Installed)
To UPM 4 CAN Card
(If Installed)
J3–8 (L) J3–8 (L) J3–8 (L) J3–8 (L)
J3–9 (H) J3–9 (H) J3–9 (H) J3–9 (H)
J3–10 (Shield) J3–10 (Shield) J3–10 (Shield) J3–10 (Shield)
Installation Information