1 of 1
OPTIONAL EATON REMOTE
EMERGENCY POWER‐OFF
082108 B
164201604-10
DESCRIPTION:
DATE:
: T E E H S : O N G N I W A R D
REVISION:
Dimensions are in millimeters [inches]
NOTE:1. Conduit and wiring between the
Remote Emergency Power‐off (REPO)
and the UPS to be supplied by the
customer.
2. Maximum distance between the
Remote EPO and the UPS not to exceed
500 feet.
3. Maximum wire size #14 AWG.
Minimum wire size #22 AWG.
NOTEInterface wiring and conduit between the REPO switch
and the UPS are to be supplied by the customer.
115.8
[4.56]
114.3
[4.50]
0.87
[0.22]
88.9
[3.50]
95.3
[3.57]
KNOCKOUT PATTERN
TYPICAL 5 SIDES
Front View
1.57
[0.40]
NEEDED
TO
REMOVE
KEY
Contact Block (Back View, Faceplate Removed)