88..22..66 MMaaxxiimmuumm CCuurrrreenntt LLoogg
Press the MMEETTEERRSS pushbutton on the main menu bar to display the Unit Meter screens. Scroll through the
meter screens using the or pushbuttons on the menu bar until the Maximum Current Log Summary screen is
displayed.
The maximum current log collects information on events where the UPS load exceeds a user–defined current
limit within a user–defined time interval. Choose a time period up to 9999 minutes and a load limit up to 100%.
The user can also select whether the limit defined is a three-phase average of the individual phase currents or
is a limit defined for each phase individually. In the first case an event is logged if the average across the
phases exceeds the defined limit within a given time period and in the second case an event is logged if any
individual phase exceeds the defined limit within a given time period. The Maximum Current Log Summary
screen displays the number of times the limit has been exceeded, the date of the last log reset, the maximum
percent of full load, and the total time over the limit. It also displays the average percent load over the limit. This
measurement differs, depending on whether a three-phase average or an individual phase measurement is
selected. Figure 37 shows the Maximum Current Log Summary screen.