Eaton 93PR 500 kW UPS
User's and Installation Guide
20
One is the creation of microclimates, which are persistent variations of temperature and/or RH within a
single room; for example one side of the room is always cooler than the other side, no matter what the
actual temperature is.
The other aspect is the rate of change of temperature and/or RH, which can occur during transitions
within the cooling system. Examples: changing the mixture ratio of inside versus outside air, or external
changes in the outside air when going from nighttime into day, and back to night.
When ignored, either one of these aspects can create an undesirable microclimate at the UPS location. If the
environment created by this microclimate exceeds the Eaton UPS operating specification, the UPS reliability,
over time, will be reduced. These same environmental extremes will also create reliability concerns for any
servers that are exposed to them.
The UPS system installation must meet the following guidelines:
The system must be installed on a level floor suitable for computer or electronic equipment. The floor
must be suitable for heavy weight and wheeling.
The system must be installed in a temperature and humidity controlled indoor area free of conductive
contaminants.
The cabinet can be installed in line-up-and-match or standalone configurations.
The UPS equipment operating environment must meet the weight requirements shown in Table in Table
3-1
:
Dimensions and
3-2
: UPS Dimensions.
Table 3-1: Dimensions
UPS 500 kW
Shipping dimensions (WxDxH) 1390 x 1220 x 2230 mm
Cabinet dimensions (WxDxH) 1200 x 1100 x 2069 mm
UPM
Shipping dimensions (WxDxH) 980 x 590 x 325 mm
UPM dimensions (WxDxH) 439 x 700 x 174.2 mm
Table 3-2: UPS cabinet weights
UPS
500 kW
Shipping weight 907 kg
Installed weight 766 kg
Floor loading 880 kg/m
2
UPM
Shipping weight 44 kg
Installed weight 39 kg