Eaton 93PR 500 kW UPS
User's and Installation Guide
75
8.3. UPS System Output
Table 8-3: UPS System Output
Number of Output Phases
Rated Output Voltage
3 phases + N
220/380 V; 230/400 V; 240/415 V, configurable
Total Voltage Harmonic Distortion
100 % Linear Load < 1 %
100 % Non-Linear Load < 5 %
Rated Output Frequency
Output Frequency Variation
Slew Rate
50 or 60 Hz, configurable
± 0,1 Hz
1 Hz/s
Overload Capability at Ambient 40 °C
(on Inverter)
60 min 102-110 % load
10 min 111-125 %
60 sec 126-150 % load
300 ms > 150 % load
Overload Capability at Ambient 40 °C
(on Inverter, Stored Energy Mode)
10 min 102-110 % load
60 sec 111-125 % load
300 ms > 125 % load
Overload Capability at Ambient 40 °C
(on Bypass)
Continuous < 125 % load
10 ms 1000 % load
Note! Bypass fuses may limit the overload capability.
Output Current
See Table
3-5
: Rated and maximum currents for rated
power and voltage on page 31
Load Power Factor, (Rated)
1. 0
Load Power Factor, (Permitted Range)
From 0.8 lagging to 0.8 leading