Table 3-6: Maximum Support Multi-core Cable Sizes
UPM QTY
Rectifier
input
(L1, L2, L3)
Bypass
input
(L1, L2, L3)
UPS
output
(380/400/415V)
(L1, L2, L3)
N PE
Battery
(BAT+, BAT-)
10*50kW 4*120mm
2
4*120mm
2
4*120mm
2
4*120mm
2
4*240mm
2
4*240mm
2
9*50kW 4*120mm
2
4*120mm
2
4*120mm
2
4*120mm
2
4*240mm
2
4*240mm
2
8*50kW 4*95mm
2
4*95mm
2
4*95mm
2
4*95mm
2
3*240mm
2
3*150mm
2
7*50kW 4*95mm
2
4*95mm
2
4*95mm
2
4*95mm
2
3*240mm
2
3*150mm
2
6*50kW 2*150mm
2
2*150mm
2
2*150mm
2
2*150mm
2
4*150mm
2
3*150mm
2
5*50kW 2*150mm
2
2*150mm
2
2*150mm
2
2*150mm
2
4*150mm
2
3*150mm
2
Table 3-7: Minimum Recommended Multi-core Cable and Fuse Sizes
UPM QTY
Rectifier
input
(L1, L2, L3)
Bypass
input
(L1, L2, L3)
UPS
output
(380/400/415V)
(L1,L2,L3)
N PE
Battery
(BAT+, BAT-)
10*50kW 3*95mm
2
3*95mm
2
3*95mm
2
3*95mm
2
5*95mm
2
5*95mm
2
9*50kW 3*95mm
2
3*95mm
2
3*95mm
2
3*95mm
2
4*95mm
2
4*95mm
2
8*50kW 3*70mm
2
3*70mm
2
3*70mm
2
3*70mm
2
4*70mm
2
4*70mm
2
7*50kW 3*70mm
2
3*70mm
2
3*70mm
2
3*70mm
2
4*70mm
2
4*70mm
2
6*50kW 2*70mm
2
2*70mm
2
2*70mm
2
2*70mm
2
3*70mm
2
3*70mm
2
5*50kW 2*70mm
2
2*70mm
2
2*70mm
2
2*70mm
2
3*70mm
2
3*70mm
2
NOTE
Bypass fuse type should be greater than 10 times rated I
2
t 20ms.