Eaton 93PR - Table 3-4: Air Conditioning or Ventilation Requirements During Full Load Operation

Eaton 93PR
92 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
Eaton 93PR 500 kW UPS
User's and Installation Guide
22
The basic environmental requirements for operation of the UPS system are:
• Ambient Temperature Range: from +5 to +40 °C
• Recommended Operating Range: from +20 to +25 °C
• Maximum Relative Humidity: 95 %, noncondensing
It is required to arrange ventilation of the UPS room. Sufficient amount of air cooling is needed to keep the
maximum room temperature rise at desired level:
Temperature rise of max. +5 °C requires the airflow of 600 m³ per 1 kVA of losses
Temperature rise of max. +10 °C requires the airflow of 300 m³ per 1 kVA of losses
An ambient temperature from +20 to +25 °C is recommended to achieve a long life of the UPS and batteries.
The cooling air entering the UPS must not exceed +40 °C. Avoid high ambient temperature, moisture, and
humidity.
The UPS ventilation requirements are shown in the following table:
Table 3-4: Air conditioning or Ventilation Requirements During Full Load Operation
Rating Heat Rejection (kVA) Heat Rejection (BTU/h x 1000)
500 kW 17915 71.1