Eaton 93PR 500 kW UPS
User's and Installation Guide
21
The UPS cabinets use forced air cooling to regulate internal component temperature. By standard, air inlets
are in the front of the cabinet and outlets are in the back. You must allow clearance in front of and behind
each cabinet for proper air circulation.
The clearances required around the UPS cabinet in both of these situations are shown in Table
3-3
: UPS
cabinet minimum clearances.
Table 3-3: UPS Cabinet Minimum Clearances
From top of cabinet
800 mm
From front of cabinet
1000 mm
From back of cabinet
800 mm
*Cabling may require more space.
A
C
B
• A = clearance at top of cabinet
• B = clearance at back of cabinet
• C = clearance at front of cabinet
Figure 3-1: UPS Cabinet Clearances. See Table
3-3
.