EasyManua.ls Logo

Eaton 93PR - 4.11. Wiring Parallel 93 PR UPS Systems; 4.11.1. Power Wiring Overview

Eaton 93PR
92 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
Eaton 93PR 500 kW UPS
User's and Installation Guide
74
8.2. UPS System Input
Table 8-2: UPS System Input
Rated Input Voltage
220/380 V; 230/400 V; 240/415 V
Voltage Tolerance, (Rectifier Input)
301 ~ 478 V Line voltage
Voltage Tolerance, (Bypass Input)
175 ~ 276 V
Phase voltage
Rated Input Frequency
50 or 60 Hz, user configurable
Frequency Tolerance
40 to 72 Hz
Number of Input Phases, (Rectifier Input)
Number of Input Phases, (Bypass Input)
3 phases + N
Input Power Factor
0.99
Rated Mains Input Current
Maximum Mains Input Current
See Table
3-5
: Rated and maximum currents for rated
power and voltage on page 31
Input Current Distortion at Rated Input Current, iTHD
< 3 %
Rectifier Ramp-up, Rectifier Start and Load Step
5 A/s per UPM (default), configurable. Min 1A/s per UPM
Backfeed Protection
Yes, for rectifier and bypass lines

Table of Contents

Other manuals for Eaton 93PR