Page 5-29
IL17569
Effective June, 2001
Table 5.7 Programmable Logic (continued)
Display Setting Description Setpoint Range/ Default Selected Refer to
Value Selection Setting Value Sec. #
Block 51P TOC Logic gate setting to block 5.5.7
51P TOC operation 9.4
9.6
Function: Select logic function to apply OR, AND, NOR, Disable
to logic gate NAND, Disable
Set Group: Select protection setting group 1, 2, 3, 4 or All 1
for logic gate to apply
IN1: Select logic type for logic input 1 * See Logic Input Options Unused
Table 5.10
IN2: Select logic type for logic input 2 * See Logic Input Options Unused
Table 5.10
IN3: Select logic type for logic input 3 * See Logic Input Options Unused
Table 5.10
IN4: Select logic type for logic input 4 * See Logic Input Options Unused
Table 5.10
Block 51R TOC Logic gate setting to block 5.5.7
51R TOC operation 9.4
9.6
Function: Select logic function to apply OR, AND, NOR, Disable
to logic gate NAND, Disable
Set Group: Select protection setting group 1, 2, 3, 4 or All 1
for logic gate to apply
IN1: Select logic type for logic input 1 * See Logic Input Options Unused
Table 5.10
IN2: Select logic type for logic input 2 * See Logic Input Options Unused
Table 5.10
IN3: Select logic type for logic input 3 * See Logic Input Options Unused
Table 5.10
IN4: Select logic type for logic input 4 * See Logic Input Options Unused
Table 5.10
Block 51X TOC Logic gate setting to block 5.5.7
51X TOC operation 9.4
9.6
Function: Select logic function to apply OR, AND, NOR, Disable
to logic gate NAND, Disable
Set Group: Select protection setting group 1, 2, 3, 4 or All 1
for logic gate to apply
IN1: Select logic type for logic input 1 * See Logic Input Options Unused
Table 5.10
IN2: Select logic type for logic input 2 * See Logic Input Options Unused
Table 5.10
IN3: Select logic type for logic input 3 * See Logic Input Options Unused
Table 5.10
IN4: Select logic type for logic input 4 * See Logic Input Options Unused
Table 5.10