9. easyE4 inside
9.1 Program execution
puts
NET sta-
tions
inputs
During this time, the easyE4 device passes through six segments in succession.
If the operands of the inputs and outputs are addressed in the easyE4, the signal states
of the digital inputs/outputs are not scanned but a memory range in the device system
memory is accessed. This memory range is called the process image. The process
image is divided into two sections: the process image for the inputs and the process
image for the outputs.
Segment 1 - 4
The easyE4 device evaluates the contact fields within the first four segments. The eval-
uation starts in the first segment in circuit diagram line 1 and continues from top to bot-
tom until circuit diagram line n is reached.
The easyE4 device then moves to the next contact segment and continues to evaluate
from top to bottom until it has reached the last contact in the fourth segment. During this
process it checks whether contacts are switched in parallel or in series and saves the
switching states of all contact fields.
Segment 5
In the fifth segment the easyE4 device assigns all coils in one pass, from the circuit dia-
gram line 1 - n, with the new switch states from the process image of the outputs.
502
easyE4 11/18 MN050009 EN www.eaton.com

Table of Contents

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Eaton easyE4 series and is the answer not in the manual?

Eaton easyE4 series Specifications

General IconGeneral
BrandEaton
ModeleasyE4 series
CategoryRelays
LanguageEnglish

Related product manuals