9. easyE4 inside
9.7 NET network
The following table can be used as a convenient guide for configuring the setting:
Number of modules: Delay with put/get Delay without put/get
ms ms
2 14 10
3 22 14
4 30 18
5 38 22
6 46 26
7 54 30
8 62 34
If you are no longer able to connect to the NET stations via Eth-
ernet with easySoft 7, set the bus delay as high as possible for
your application. To do this, you will need to disconnect each
device from the Ethernet and use easySoft 7 to change the bus
delay point by point.
easyE4 11/18 MN050009 EN www.eaton.com
515