EDR-5000 IM02602007E
Options of the DNP
Name Description
-.- No assignment
Prot.FaultNo Waveform No.
Prot.No of GridFaults Number of grid faults: A grid fault, e.g. a short circuit, might cause several faults with trip and autoreclosing,
each fault being identified by an increased fault number. In this case, the grid fault number remains the same.
Bkr.TripCmd Cr Counter: Total number of trips of the switchgear (breaker, load break switch…). Resettable with Total or All.
LVRT [1].NumOf Vdips in t-
LVRT
Number of Voltage dips during t-LVRT
LVRT [1].Cr Tot Numb of Vdips Counter Total number of voltage dips.
LVRT [1].Cr Tot Numb of Vdips
to Trip
Counter Total number of voltage dips that caused a Trip.
LVRT [2].NumOf Vdips in t-
LVRT
Number of Voltage dips during t-LVRT
LVRT [2].Cr Tot Numb of Vdips Counter Total number of voltage dips.
LVRT [2].Cr Tot Numb of Vdips
to Trip
Counter Total number of voltage dips that caused a Trip.
AR.AR Shot No. Counter - Auto Reclosure Attempts
AR.Total number Cr Total number of all executed Automatic Reclosures Attempts
AR.Cr successfl Total number of successfully executed Automatic Reclosures
AR.Cr failed Total number of unsuccessfully executed automatic reclosure attempts
AR.Cr Service Alarm1 Remaining numbers of ARs until Service Alarm 1
AR.Cr Service Alarm2 Remaining numbers of ARs until Service Alarm 2
AR.Max Shots / h Cr Counter for the maximum allowed shots per hour.
ECr.Wh Fwd Positive Active Power is consumed active energy
ECr.Wh Rev Negative Active Power (Fed Energy)
ECr.VArh Lag Positive Reactive Power is consumed Reactive Energy
ECr.VArh Lead Negative Reactive Power (Fed Energy)
Sys.Operating hours Cr Operating hours counter of the protective device
Selectable Switchgears of the DNP
Name Description
-.- No assignment
Bkr.State Signal: Breaker Position (0 = Indeterminate, 1 = OPEN, 2 = CLOSE, 3 = Disturbed)
www.eaton.com 348