EDR-5000 IM02602007E
Switch Direction Control
Switching commands are validated before execution. When the switchgear is already in the desired position, the switch
command will not be issued again. An opened breaker cannot be opened again. This also applies for switching
command at the HMI or via SCADA.
Anti Pumping
By pressing the CLOSE command softkey only a single switching CLOSE impulse will be issued independent, how long
the softkey is actuated. The switchgear will close only once per close command.
Direct Commands of the Control
Parameter Description Setting range Default Menu path
Res Bwear Sl
Breaker
Resetting the slow breaker alarm Inactive,
Active
Inactive [Operation
/Reset]
Ack TripCmd Acknowledge Trip Command Inactive,
Active
Inactive [Operation
/Reset]
Global Protection Parameters of the Control
Parameter Description Setting range Default Menu path
CinBkr-52a The breaker is in CLOSE-position if the state of the
assigned signal is true (52a).
1..n, Dig Inputs DI-8P X1.DI 5 [Control
/Bkr
/Pos Indicatrs
Wirng]
CinBkr-52b The breaker is in OPEN-position if the state of the
assigned signal is true (52b).
1..n, Dig Inputs DI-8P X1.DI 6 [Control
/Bkr
/Pos Indicatrs
Wirng]
Ready Breaker is ready for operation if the state of the assigned
signal is true. This digital input can be used by some
protective elements (if they are available within the
device) like Auto Reclosure (AR), e.g. as a trigger signal.
1..n, Dig Inputs -.- [Control
/Bkr
/Pos Indicatrs
Wirng]
www.eaton.com 425