EDR-5000 IM02602007E
Option 2 – Connecting a Module Input with a Digital Input
Call a module. Within this module assign a Digital Input onto a module input. Example: A protection module
should be blocked depending on the state of a Digital Input.. For this assign onto the blocking input within the
Global Parameters the Digital Input (e.g. Ex Blo 1).
Checking the Assignments of a Digital Input
In order to check the targets that a Digital Input is assigned to please proceed as follows:
Call up menu [Device Parameter\Digital Inputs].
Navigate to the Digital Input that should be checked.
At the HMI:
A multiple assignment, that means if a Digital Input is used more than once (if it is assigned to multiple targets), this will
be indicated by an ”...” behind a Digital Input. Call up this Digital Input by Softkey »Arrow right« in order to see the list of
targets of this Digital Input.