EasyManua.ls Logo

Eaton EDR-5000 - Page 925

Eaton EDR-5000
1041 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
EDR-5000 IM02602007E
PQ-protection:
32[x]/32V[x]
Accuracy
Threshold ±3% or ±0.1% VAn
Dropout Ratio 97% or 1 VA for Over-protection
103% or 1 VA for Under-protection
for setting values ≤ 0.1 Sn:
60% or 0.5 VA for Over-protection
140% or 0.5 VA for Under-protection
for setting values ≤ 0.01 Sn
60% or 0.2 VA for Over-protection
140% or 0.2 VA for Under-protection
t ±1% or ±10 ms
Operating time <100 ms
75 ms typically
Disengaging time 100 ms
*1) Common reference conditions: at |PF|>0.5, symmetrically fed, at fn and 0.8 - 1.3 x Vn (Vn=100V)
Auto Reclosing:
AR
Accuracy
t (all timers) ±1% or ±20 ms
Sync-Check:
Sync
Accuracy
Voltage measurement ±1.5% of the setting value or 1% Vn
Slip Frequency measurement ±20 mHz at fn
Angle measurement ±2°
Angle Compensation measurement ±4°
t (all timers) ±1% or ±10 ms
Q->&V< / Decoupling Tolerance
I min QV ±1.5% of the setting value or ±1% In
Dropout Ratio 95% or 0.5% In
VLL< QV ±1,5% of the setting value or ±1% Vn
Dropout Ratio 102% or 0.5% Vn
Phi-Power ±1°
Q min QV ±3% of the setting value or ±0.1% Sn
Dropout Ratio 95%
t1-QV ±1% or ±10 ms
t2-QV ±1% or ±10 ms
Operating Time <40 ms
Disengaging Time <40 ms
www.eaton.com 925

Table of Contents

Other manuals for Eaton EDR-5000

Related product manuals