EDR-5000 IM02602007E
ReCon / Release Para Tolerance
VLL-Release ±1.5% of the setting value or ±1% Vn
Dropout Ratio 98% or 0.5% Vn for VLL>
102% or 0.5% Vn for VLL<
f ±20 mHz at fn
Dropout < 0.05% fn
t-Release ±1% or ±10 ms
Operating Time <40 ms
UFLS Tolerance
I min ±1.5% of the setting value or ±1% In
Dropout Ratio 95% or 0.5% In
V min ±1.5% of the setting value or ±1% Vn
Dropout Ratio 98% or 0.5% Vn
Phi-Power ±2°
P min ±5% of the setting value or ±0.1% Sn
Dropout Ratio 95% or 0.5 W
f< ±10 mHz at fn
Dropout < 0.05% fn
t-UFLS ±1% or ±10 ms
Operating time
Starting from f lower than f< - 0.02 Hz
- 0.1 Hz
- 2.0 Hz
<100 ms
typically 70 ms
typically 50 ms
Disengaging time <120 ms
Switch onto Fault:
SOTF
Accuracy
Operating time <35 ms
I< ±1.5% of the setting value or1% In
t-enable ±1% or ±10 ms
Cold Load Pickup:
CLPU
Accuracy
Threshold ±1.5% of the setting value or1% In
Operating time <35 ms
I< ±1.5% of the setting value or1% In
t-Load OFF ±1% or ±15 ms
t-Max Block ±1% or ±15 ms
Settle Time ±1% or ±15 ms
Breaker Failure Protection:
50BF
Accuracy
I-BF> ±1.5% of the setting value or1% In
t-BF ±1% or ±10 ms
Operating Time
Starting from I Higher than 1.3 x I-BF>
<40 ms
Disengaging Time <40 ms
www.eaton.com 926