USING THE IPMI TOOL SET
EATON Managed ePDUt User’s Guide S 164201xxx Rev 1 DRAFT 10−OCT−2008
104
Set Socket ACL
Request Data
1 Socket number
2 Number of ACL entries to follow
3
+N
ACL entry
[7] 0b = deny, 1b = allow
[6] 0b = user id, 1b = privilege level
[5–0] user id or privilege level depending on [6]
Response Data 1 Completion Code
Get Socket ACL
Request Data 1 Socket number
Response Data
1 Completion Code
2 Number of ACL entries to follow
3
+N
ACL entry
[7] 0b = deny, 1b = allow
[6] 0b = user id, 1b = privilege level
[5−0] user id or privilege level depending on [6]
Set Sensor Calibration
Sensor calibration is only allowed for threshold−based sensors that return a sensor
reading byte with the Get Sensor Reading command. Also, not all threshold−based
sensors have the capability to be calibrated.
Request Data
1 Sensor number (fhh = reserved)
2 Actual sensor reading value.
Assumes, that at the time this command is executed a calibrated
measurement is applied to the sensor.
Response Data 1 Completion Code
00h – If calibration OK
CDh – If the sensor cannot be calibrated
Test Actors
Used for hardware testing during production.
Request Data 1 [7–2] reserved
[1] Beeper test, 0b = disable, 1b = enable
[0] 7 segment display test, 0b = disable, 1b = enable
Response Data 1 Completion Code