USING THE WEB INTERFACE
EATON Managed ePDUt User’s Guide S 164201xxx Rev 1 DRAFT 10−OCT−2008
55
Setting the ePDU Thresholds
To set the ePDU thresholds:
1. Select Device Settings, and then select Unit Setup. The Unit Setup page displays
(see Figure 51).
Figure 51. Unit Setup Page
2. Type a number in the Delay until outlets are switched on again after outlet reset field.
When the outlets on the ePDU are power cycled, they are turned off and then
back on. The number you enter here determines the length of time (in seconds) it
takes for the outlets to turn back on after they are shut down during the power
cycle. The default is 10 seconds.
NOTE The number you enter here applies to all outlets on the ePDU. However, you can override this
number for specific outlets. See Setting Outlet Thresholds" on page 58. You can power cycle an outlet from
the Outlet Details page. See Power Cycling an Outlet" on page 59 for instructions.
3. Type a number of seconds in the Sequence Delay field. The default is
200 milliseconds.
4. Set the RMS voltage, current, and temperature thresholds for the ePDU in the
Thresholds panel. For each setting, enter critical and non−critical thresholds.
5. Click Apply. The delays and thresholds are applied.