UPS Installation Plan and Unpacking
Eaton
®
Power Xpert
®
9395P-900 UPS Installation and Operation Manual P-164000501—Rev 09 www.eaton.com/powerquality 3-5
Table 3-5. 400V Air Conditioning or Ventilation Requirements During Full Load Operation
Model Rating
Input/Output
Voltage
Heat Rejection
kW (1000 BTU/hr)
Ventilation Required for Cooling Air Exhaust
Eaton 9395P-900/825
(CSS)
825kVA
825 kW
400/400 34.0 (116.1)
Approximately 3300 liter/sec (7000 CFM)
With field installed UPM:
Approximately 4250 liter/sec (9000 CFM)
Eaton 9395P-900/750
(CSS)
750 kVA
750 kW
400/400 30.9 (105.6)
Eaton 9395P-900/675
(CSS)
675 kVA
675 kW
400/400 27.8 (95.0)
Eaton 9395P-900/600
(CSS)
600 kVA
550 kW
400/400 24.7 (84.5)
Approximately 2400 liter/sec (5000 CFM)
Eaton 9395P-900/550
(CSS)
550 kVA
550 kW
400/400 22.7 (77.4)
Eaton 9395P-900/500
(CSS)
500 kVA
500 kW
400/400 20.6 (70.4)
Eaton 9395P-900/450
(CSS)
450 kVA
450 kW
400/400 18.5 (63.3)
NOTE CSS = Continuous Static Switch; IOM = Input Output Module
Table 3-6. 380V Air Conditioning or Ventilation Requirements During Full Load Operation
Model Rating
Input/Output
Voltage
Heat Rejection
kW (1000 BTU/hr)
Ventilation Required for Cooling Air Exhaust
Eaton 9395P-900/825
(CSS)
825kVA
825 kW
380/380 34.0 (116.1)
Approximately 3300 liter/sec (7000 CFM)
With field installed UPM:
Approximately 4250 liter/sec (9000 CFM)
Eaton 9395P-900/750
(CSS)
750 kVA
750 kW
380/380 30.9 (105.6)
Eaton 9395P-900/675
(CSS)
675 kVA
675 kW
380/380 27.8 (95.0)
Eaton 9395P-900/600
(CSS)
600 kVA
550 kW
380/380 24.7 (84.5)
Approximately 2400 liter/sec (5000 CFM)
Eaton 9395P-900/550
(CSS)
550 kVA
550 kW
380/380 22.7 (77.4)
Eaton 9395P-900/500
(CSS)
500 kVA
500 kW
380/380 20.6 (70.4)
Eaton 9395P-900/450
(CSS)
450 kVA
450 kW
380/380 18.5 (63.3)
NOTE CSS = Continuous Static Switch; IOM = Input Output Module