EasyManua.ls Logo

Eaton Power Xpert 9395P-900 Series - Page 38

Eaton Power Xpert 9395P-900 Series
232 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
UPS Installation Plan and Unpacking
3-4 Eaton
®
Power Xpert
®
9395P-900 UPS Installation and Operation Manual
P-164000501—Rev 09 www.eaton.com/powerquality
The UPS ventilation requirements are shown in Table 3-3.
Table 3-3. 480V Air Conditioning and Ventilation Requirements During Full Load Operation
Model Rating
Input/Output
Voltage
Heat Rejection
kW (1000 BTU/hr)
Ventilation Required for Cooling Air Exhaust
Eaton 9395P-900/900*
(CSS)
900 kVA
900 kVA
480/480 34.6 (118)
Approximately 3300 liter/sec (7000 CFM)
With field installed UPM:
Approximately 4250 liter/sec (9000 CFM)
Eaton 9395P-900/900
(CSS or IOM)
900 kVA
825 kW
480/480 31.7 (108.3)
Eaton 9395P-900/825
(CSS)
825kVA
825 kW
480/480 31.7 (108.3)
Eaton 9395P-900/750
(CSS)
750 kVA
750 kW
480/480 28.0 (95.6)
Eaton 9395P-900/675
(CSS)
675 kVA
675 kW
480/480 23.8 (81.1)
Eaton 9395P-900/600*
(CSS)
600 kVA
600 kVA
480/480 23.1 (78.7)
Approximately 2400 liter/sec (5000 CFM)
Eaton 9395P-900/600
(CSS)
600 kVA
550 kW
480/480 21.1 (72.2)
Eaton 9395P-900/550
(CSS)
550 kVA
550 kW
480/480 21.1 (72.2)
Eaton 9395P-900/500
(CSS)
500 kVA
500 kW
480/480 18.7 (63.8)
Eaton 9395P-900/450
(CSS)
450 kVA
450 kW
480/480 15.8 (54.1)
NOTE CSS = Continuous Static Switch; IOM = Input Output Module
Table 3-4. 415V Air Conditioning and Ventilation Requirements During Full Load Operation
Model Rating
Input/Output
Voltage
Heat Rejection
kW (1000 BTU/hr)
Ventilation Required for Cooling Air Exhaust
Eaton 9395P-900/825
(CSS)
825kVA
825 kW
415/415 34.0 (116.1)
Approximately 3300 liter/sec (7000 CFM)
With field installed UPM:
Approximately 4250 liter/sec (9000 CFM)
Eaton 9395P-900/750
(CSS)
750 kVA
750 kW
415/415 30.9 (105.6)
Eaton 9395P-900/675
(CSS)
675 kVA
675 kW
415/415 27.8 (95.0)
Eaton 9395P-900/600
(CSS)
600 kVA
550 kW
415/415 24.7 (84.5)
Approximately 2400 liter/sec (5000 CFM)
Eaton 9395P-900/550
(CSS)
550 kVA
550 kW
415/415 22.7 (77.4)
Eaton 9395P-900/500
(CSS)
500 kVA
500 kW
415/415 20.6 (70.4)
Eaton 9395P-900/450
(CSS)
450 kVA
450 kW
415/415 18.5 (63.3)
NOTE CSS = Continuous Static Switch; IOM = Input Output Module