UPS Installation Plan and Unpacking
Eaton
®
Power Xpert
®
9395P-900 UPS Installation and Operation Manual P-164000501—Rev 09 www.eaton.com/powerquality 3-33
Table 3-24. 400V/380V Power Cable Conduit Requirements
UPS Model Voltage Terminal
Number of
Wires in Conduit
Minimum Conduit
Trade Size
Number of
Conduits
Eaton 9395P-900/825
400 Vac
380 Vac
AC Input to UPS Rectifier
(A, B, C, Ground)
838
AC Input to Bypass and Output
(A, B, C, Ground)
636
DC
(Common Battery)
Battery
(Positive, Negative, Ground)
10 3.5 5
Eaton 9395P-900/750
400 Vac
380 Vac
AC Input to UPS Rectifier
(A, B, C, Ground)
838
AC Input to Bypass and Output
(A, B, C, Ground)
636
DC
(Common Battery)
Battery
(Positive, Negative, Ground)
8 3.5 4
Eaton 9395P-900/675
400 Vac
380 Vac
AC Input to UPS Rectifier
(A, B, C, Ground)
636
AC Input to Bypass and Output
(A, B, C, Ground)
636
DC
(Common Battery)
Battery
(Positive, Negative, Ground)
6 3.5 4
Eaton 9395P-900/600
400 Vac
380 Vac
AC Input to UPS Rectifier
(A, B, C, Ground)
636
AC Input to Bypass and Output
(A, B, C, Ground)
535
DC
(Common Battery)
Battery
(Positive, Negative, Ground)
838
Eaton 9395P-900/550
400 Vac
380 Vac
AC Input to UPS Rectifier
(A, B, C, Ground)
636
AC Input to Bypass and Output
(A, B, C, Ground)
434
DC
(Common Battery)
Battery
(Positive, Negative, Ground)
636
Eaton 9395P-900/500
400 Vac
380 Vac
AC Input to UPS Rectifier
(A, B, C, Ground)
535
AC Input to Bypass and Output
(A, B, C, Ground)
434
DC
(Common Battery)
Battery
(Positive, Negative, Ground)
636