EasyManua.ls Logo

Eaton Power Xpert 9395P-900 Series - Page 66

Eaton Power Xpert 9395P-900 Series
232 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
UPS Installation Plan and Unpacking
3-32 Eaton
®
Power Xpert
®
9395P-900 UPS Installation and Operation Manual
P-164000501—Rev 09 www.eaton.com/powerquality
Table 3-23. 415V Power Cable Conduit Requirements
UPS Model Voltage Terminal
Number of Wires
in Conduit
Minimum Conduit
Trade Size
Number of
Conduits
Eaton 9395P-900/825
415 Vac
AC Input to UPS Rectifier
(A, B, C, Ground)
838
AC Input to Bypass and Output
(A, B, C, Ground)
636
DC
(Common Battery)
Battery
(Positive, Negative, Ground)
10 3.5 5
Eaton 9395P-900/750
415 Vac
AC Input to UPS Rectifier
(A, B, C, Ground)
838
AC Input to Bypass and Output
(A, B, C, Ground)
636
DC
(Common Battery)
Battery
(Positive, Negative, Ground)
8 3.5 4
Eaton 9395P-900/675
415 Vac
AC Input to UPS Rectifier
(A, B, C, Ground)
636
AC Input to Bypass and Output
(A, B, C, Ground)
535
DC
(Common Battery)
Battery
(Positive, Negative, Ground)
8 3.5 4
Eaton 9395P-900/600
415 Vac
AC Input to UPS Rectifier
(A, B, C, Ground)
636
AC Input to Bypass and Output
(A, B, C, Ground)
535
DC
(Common Battery)
Battery
(Positive, Negative, Ground)
838
Eaton 9395P-900/550
Eaton 9395P-900/500
415 Vac
AC Input to UPS Rectifier
(A, B, C, Ground)
535
AC Input to Bypass and Output
(A, B, C, Ground)
434
DC
(Common Battery)
Battery
(Positive, Negative, Ground)
636
Eaton 9395P-900/450
See Note 1
415 Vac
AC Input to UPS Rectifier
(A, B, C, Ground)
434
AC Input to Bypass and Output
(A, B, C, Ground)
333
DC
(Common Battery)
Battery
(Positive, Negative, Ground)
636
All models
DC
(Separate Battery -
per UPM)
Battery
(Positive, Negative, Ground)
741
NOTE 1V Because of the future upgradability to a fully rated 415V 825 kVA UPS with the addition of the FI-UPM, these conduit sizes are specified
for an 825 kVA UPS.
NOTE 2V Bypass conduit data is not applicable to IOM configurations.
Battery Conductor Routing: Refer to the notes at the bottom of Tables 3-7 Input/Output Ratings and External Wiring Requirements.

Table of Contents

Related product manuals