UPS Installation Plan and Unpacking
Eaton
®
Power Xpert
®
9395P-900 UPS Installation and Operation Manual P-164000501—Rev 09 www.eaton.com/powerquality 3-31
NOTE 1V Because of the future upgradability to a fully rated 480V 900 kVA UPS with the addition of the FI-UPM, these conduit sizes are specified
for a 900 kVA UPS.
NOTE 2V Bypass conduit data is not applicable to IOM configurations.
Battery Conductor Routing: Refer to the notes at the bottom of Tables 3-7 Input/Output Ratings and External Wiring Requirements.
Table 3-22. 480V Power Cable Conduit Requirements
UPS Model Voltage Terminal
Number of
Wires in
Conduit
Minimum Conduit
Trade Size
Number of
Conduits
Eaton 9395P-900/900*
Eaton 9395P-900/900
Eaton 9395P-900/825
480 Vac
AC Input to UPS Rectifier
(A, B, C, Ground)
435
AC Input to Bypass and Output
(A, B, C, Ground)
434
DC
(Common
Battery)
Battery
(Positive, Negative, Ground)
5 3.5 5
Eaton 9395P-900/750
Eaton 9395P-900/675
480 Vac
AC Input to UPS Rectifier
(A, B, C, Ground)
434
AC Input to Bypass and Output
(A, B, C, Ground)
433
DC
(Common
Battery)
Battery
(Positive, Negative, Ground)
5 3.5 4
Eaton 9395P-900/600*
Eaton 9395P-900/600
Eaton 9395P-900/550
Eaton 9395P-900/500
Eaton 9395P-900/450
See Note 1
480 Vac
AC Input to UPS Rectifier
(A, B, C, Ground)
435
AC Input to Bypass and Output
(A, B, C, Ground)
434
DC
(Common
Battery)
Battery
(Positive, Negative, Ground)
5 3.5 5
All models
DC
(Separate
Battery -
per UPM)
Battery
(Positive, Negative, Ground)
741