UPS Installation Plan and Unpacking
3-30 Eaton
®
Power Xpert
®
9395P-900 UPS Installation and Operation Manual
P-164000501—Rev 09 www.eaton.com/powerquality
Conduit sizes were chosen from NEC Table 4, Electrical Metallic Tubing (EMT). See Table 3-23 for conduit
requirements.
Per NEC article 300, 3(B)(1), all three-phase conductors must be run in the same conduit.
Conduit is sized to accommodate one neutral conductor the same size as the phase conductor and one ground
conductor sized in accordance with NEC Table 250.122.
Conduit sizes listed are for copper wiring only.
Table 3-20. Supplied External Wiring Terminal Hardware Kit
Part Size Quantity Terminals Used On Eaton Part Number
Bolt, Grade 5 M12 x 40 mm 30 Ground and Neutral 180190078-112
Bolt, Grade 5 M12 x 50 mm 86
Rectifier Input, Bypass Input, Battery Input,
Output
180190078-115
Flat Washer M12 202
Rectifier Input, Bypass Input, Battery Input,
Output, and Ground
180500036-120
Conical Washer M12 116
Rectifier Input, Bypass Input, Battery Input,
Output, and Ground
180500037-120
Nut M12 86
Rectifier Input, Bypass Input, Battery Input,
Output, and Ground
180200001-07
NOTE Bypass terminations are not applicable to IOM configurations.
Table 3-21. Recommended Installation Parts and Tools (Not Supplied by Eaton)
Part Size Quantity Manufacturer Part Number Notes
Long Barrel 2-Hole Lug
2/0 AWG
As required
Thomas & Betts 54862BE
Copper wire only
3/0 AWG Thomas & Betts 54864BE
4/0 AWG Thomas & Betts 54866BE
250 MCM Thomas & Betts 54868BE
300 MCM Thomas & Betts 54870BE
350 MCM Thomas & Betts 54872BE
400 MCM Thomas & Betts 54874BE
500 MCM Thomas & Betts 54876BE
Manual Hydraulic Crimp Tool 14 Ton 1 Thomas & Betts TBM14M
Die Set N/A 1 Thomas & Betts 15506