144 Eaton Power Xpert 9395 UPS Installation and Operation Manual 164201764—Rev 14
Table 33. Command Menu Operation (Continued)
Function Sub-function Operation
Enable (Disable) Var Module Management
Enables or disables the Variable Module Management
System mode. Enable changes to Disable when the Variable
Module Management System mode is enabled.
Start High Alert Starts High Alert mode.
Load Off
Displays the Load Off screen (see paragraph
7.2.7 Load Off Screen).
Charger Control
Commands
Use the up or down arrow pushbutton to highlight the
command function desired, then press the SELECT
pushbutton to execute the command.
Charger On Turns the battery charger on.
Charger Off Turns the battery charger off.
UPM Control
Commands
Use the up or down arrow pushbutton to highlight the
command function desired, then press the SELECT
pushbutton to execute the command.
UPM On Turns the UPM on without transferring the load to Online
mode. The Load is on bypass.
UPM Off Transfers the load to bypass and turns the UPM off.
UPM Go to Online Turns the UPM on and transfers the load to Online mode.
Charger On Turns the battery charger on.
Charger Off Turns the battery charger off.
NOTE The Energy Saver System and Variable Module Management System mode commands are displayed only if enabled at the
factory or by an Eaton Customer Service Engineer.
NOTE Variable Module Management System and Energy Saver System modes are mutually exclusive.
77..33 SSiinnggllee UUPPSS OOppeerraattiioonn
The paragraphs in this section provide operating instructions for a UPS system containing only one UPS.
NOTE A Field Installed UPM (FI-UPM) is always designated as UPM 4.
77..33..11 SSttaarrttiinngg tthhee UUPPSS iinn OOnnlliinnee MMooddee
To start the UPS system:
1. Unfasten the front door latch and swing the door open (see Figure 17).
NOTE *Only perform steps 2 and 5 if the UPS has an input breaker CB1 (see Figure 79).
2. *Verify that input breaker CB1 is open.
3. Close the UPS input feeder circuit breaker.
4. Close the UPS Bypass input feeder circuit breaker.
5. *Close input breaker CB1.
UPS Operating Instructions