Table 20. Connection sizes and torques.
Output rating Size and torque
Input voltage
Frame
size
Drive
catalog
number
CT/I
H
current
amps
VT/I
L
current
amps
Power
wire size
AWG
(mm
2
)
Power wire
torque
in.-lb (N·m)
Ground
wire size
AWG
(mm
2
)
Ground
wire
torque
in.-lb (N·m)
Control
wire size
AWG (mm
2
)
Control
wire torque
in.-lb (N·m)
AI/DI RO
200 Vac to
240 Vac
50/60 Hz
3-phase
FR1 DM1-321D6… 1.6 2.5 14 (2.5) 4.4 (0.5) 14 (2.5) 7.1 (0.8) 28-16 (0.5-1.5) 1.73 (0.2) 4.5 (0.5)
DM1-323D0… 3 4.8 14 (2.5) 4.4 (0.5) 14 (2.5) 7.1 (0.8) 28-16 (0.5-1.5) 1.73 (0.2) 4.5 (0.5)
DM1-324D8… 4.8 7.8 14 (2.5) 4.4 (0.5) 12 (2.5) 7.1 (0.8) 28-16 (0.5-1.5) 1.73 (0.2) 4.5 (0.5)
DM1-327D8… 7.8 11 12 (4) 4.4 (0.5) 10 (4) 7.1 (0.8) 28-16 (0.5-1.5) 1.73 (0.2) 4.5 (0.5)
FR2 DM1-32011… 11 17.5 10 (6) 10.5 (1.2) 10 (6) 7.1 (0.8) 28-16 (0.5-1.5) 1.73 (0.2) 4.5 (0.5)
DM1-32017… 17.5 25.3 8 (10) 10.5 (1.2) 10 (10) 7.1 (0.8) 28-16 (0.5-1.5) 1.73 (0.2) 4.5 (0.5)
FR3 DM1-32025… 25.3 32.2 8 (10) 10.5 (1.2) 8 (10) 14.2 (1.6) 28-16 (0.5-1.5) 1.73 (0.2) 4.5 (0.5)
FR4 DM1-32032… 32.2 48.3 4 (25) 33 (3.73) 8 (16) 14.2 (1.6) 28-16 (0.5-1.5) 1.73 (0.2) 4.5 (0.5)
DM1-32048… 48.3 62.1 3 (35) 33 (3.73) 6 (16) 14.2 (1.6) 28-16 (0.5-1.5) 1.73 (0.2) 4.5 (0.5)
380 Vac to
480 Vac
50/60 Hz
3-phase
FR1 DM1-341D5… 1.5 2.2 14 (2.5) 4.4 (0.5) 14 (2.5) 7.1 (0.8) 28-16 (0.5-1.5) 1.73 (0.2) 4.5 (0.5)
DM1-342D2… 2.2 4.3 14 (2.5) 4.4 (0.5) 14 (2.5) 7.1 (0.8) 28-16 (0.5-1.5) 1.73 (0.2) 4.5 (0.5)
DM1-344D3… 4.3 5.6 14 (2.5) 4.4 (0.5) 14 (2.5) 7.1 (0.8) 28-16 (0.5-1.5) 1.73 (0.2) 4.5 (0.5)
DM1-345D6… 5.6 7.6 14 (2.5) 4.4 (0.5) 10 (2.5) 7.1 (0.8) 28-16 (0.5-1.5) 1.73 (0.2) 4.5 (0.5)
FR2 DM1-347D6… 7.6 12 12 (4) 10.5 (1.2) 10 (4) 7.1 (0.8) 28-16 (0.5-1.5) 1.73 (0.2) 4.5 (0.5)
DM1-34012… 12 16 10 (6) 10.5 (1.2) 10 (6) 7.1 (0.8) 28-16 (0.5-1.5) 1.73 (0.2) 4.5 (0.5)
DM1-34016… 16 23 8 (10) 10.5 (1.2) 10 (10) 7.1 (0.8) 28-16 (0.5-1.5) 1.73 (0.2) 4.5 (0.5)
FR3 DM1-34023.. 23 31 8 (10) 10.5 (1.2) 8 (10) 14.2 (1.6) 28-16 (0.5-1.5) 1.73 (0.2) 4.5 (0.5)
FR4 DM1-340 31… 31 38 6 (16) 33 (3.73) 8 (16) 14.2 (1.6) 28-16 (0.5-1.5) 1.73 (0.2) 4.5 (0.5)
DM1-34038… 38 46 4 (25) 33 (3.73) 8 (16) 14.2 (1.6) 28-16 (0.5-1.5) 1.73 (0.2) 4.5 (0.5)
525 Vac to
600 Vac
50/60 Hz
3-phase
FR2 DM1-354D5… 4.5 7.5 - - - - 28-16 (0.5-1.5) 1.73 (0.2) 4.5 (0.5)
DM1-357D5… 7.5 10 - - - - 28-16 (0.5-1.5) 1.73 (0.2) 4.5 (0.5)
DM1-35010… 10 13.5 - - - - 28-16 (0.5-1.5) 1.73 (0.2) 4.5 (0.5)
FR3 DM1-35013… 13.5 18 - - - - 28-16 (0.5-1.5) 1.73 (0.2) 4.5 (0.5)
FR4 DM1-35018… 18 22 - - - - 28-16 (0.5-1.5) 1.73 (0.2) 4.5 (0.5)
DM1-35022… 22 27 - - - - 28-16 (0.5-1.5) 1.73 (0.2) 4.5 (0.5)
Notes:
Line and motor cable size is selected according to UL 61800-5-1 for copper conductor rated 75°C. Use only with copper wire rated 75°C here. Size requirements for
other different wire types are defined in the National Electrical Code
®
, ANSI/NFPA
®
70.
Earthing conductor size is determined by the maximum overcurrent device rating used ahead of the drive according to UL 61800-5-1.
If power cubes or bypass are used, a UL listed Class J, T, CF, CC or equivalent fuse is recommended.
(continued).