49
Appendix B—Installation guidelines
POWERXL SERIES VFDS MN040060EN—September 2020 www.eaton.com
Appendix B—Installation guidelines
Cable and fuse sizing
Table 28. UL cable and fuse sizes (continued).
Output rating Input rating UL application
Input
voltage
Frame
size
Drive
catalog
number
CT/I
H
current
amps
VT/I
L
current
amps
CT/I
H
current
amps
VT/I
L
current
amps
Recom-
mended
fuse
(Class
J, T, CF
or CC)
(max
rating)
100
kAIC①
Recom-
mended
miniature
inverse-
time
molded-
case
circuit
breaker
(max
rating)
10/14
kAIC①
Recom-
mended
Type E CMC
(max rating)
65 kAIC②
Recom-
mended
inverse-
time
molded-
case
circuit
breaker
(max
rating)
100 kAIC
(open type
only for
3-phase)①
NEC
wire
size
line
and
motor
AWG
NEC
wire
size
ground
AWG
Term-
inal
size
line
and
motor
AWG
Term-
inal
size
ground
AWG
100 Vac
to 120
Vac
50/60
Hz
1-phase
FR1 DM1-
111D6…
1.6 2.5 6.4 10 30 30 \ 30 14 10 18-8 16-8
DM1-
113D0…
3 4.8 13.5 20 70 63 \ 70 10 8 18-8 16-8
FR2 DM1-
114D8…
4.8 6.9 20 26.4 90 63 \ 90 8 8 20-6 12-6
DM1-
116D9…
6.9 7.8 26.4 30 125 63 \ 125 8 6 20-6 12-6
200 Vac
to 240
Vac
50/60
Hz
1-phase
FR1 DM1-
121D6…
1.6 2.5 4 6.5 15 15 \ 15 14 14 18-8 16-8
DM1-
123D0…
3 4.8 8 11 30 30 \ 30 14 10 18-8 16-8
DM1-
124D8…
4.8 7.8 11 17 60 63 \ 60 10 8 18-8 16-8
FR2 DM1-
127D8…
7.8 11 18 23 80 63 \ 80 10 8 20-6 12-6
DM1-
12011…
11 17.5 23 35 125 63 \ 125 8 6 20-6 12-6
FR3 DM1-
12 0 17…
17.5 25.3 38 49.6 200 \ \ 200 6 6 20-6 8-6
200 Vac
to 240
Vac
50/60
Hz
3-phase
FR1 DM1-
321D6…
1.6 2.5 2.1 3.3 6 FAZ-C5/3-
NA
(10kA)
XTPR6P3BC1 +
XTPAXLSA or
PKZM0-6.3 +
BK25/3-PKZ0-E
EGC3015FFG 14 14 18-8 16-10
DM1-
323D0…
3 4.8 3.9 5.8 15 FAZ-C10/3-
NA
(10kA)
XTPR6P3BC1 +
XTPAXLSA or
PKZM0-6.3 +
BK25/3-PKZ0-E
EGC3015FFG 14 14 18-8 16-10
DM1-
324D8…
4.8 7.8 5.8 9.4 20 FAZ-C15/3-
NA
(14k A)
XTPR010BC1 +
XTPAXLSA or
PKZM0-10 +
BK25/3-PKZ0-E
EGC3015FFG 14 12 18-8 16-10
DM1-
327D8…
7.8 11 9.4 13.2 30 FAZ-C20/3-
NA
(14k A)
XTPR016DC1 +
XTPAXLSAD or
PKZM4-16 +
BK50/3-PKZ4-E
EGC3020FFG 12 10 18-8 16-10
.