Table 16. Approximate space requirements in inches (mm).
Output rating Mounting clearance imperial Airflow
Input voltage Frame size
Drive
catalog
number
CT/IH
current
amps
VT/IL
current
amps
A
in. (mm)
B
in. (mm)
C
in. (mm)
D
in. (mm) CFM (m3/h)
100 Vac to 120
Vac, 50/60 Hz
1-phase
FR1 DM1-111D6… 1.6 2.5 0 0 1.97 (50) 1.97 (50) 14.83 (25.2)
DM1-113D0… 3 4.8 0 0 1.97 (50) 1.97 (50) 14.83 (25.2)
FR2 DM1-114D8… 4.8 6.9 0 0 1.97 (50) 1.97 (50) 24.72 (42)
DM1-116D9… 6.9 7.8 0 0 1.97 (50) 1.97 (50) 24.72 (42)
200 Vac to 240
Vac, 50/60 Hz
1-phase
FR1 DM1-121D6… 1.6 2.5 0 0 1.97 (50) 1.97 (50) 14.83 (25.2)
DM1-123D0… 3 4.8 0 0 1.97 (50) 1.97 (50) 14.83 (25.2)
DM1-124D8… 4.8 7.8 0 0 1.97 (50) 1.97 (50) 14.83 (25.2)
FR2 DM1-127D8… 7.8 11 0 0 1.97 (50) 1.97 (50) 24.72 (42)
DM1-12011… 11 17.5 0 0 1.97 (50) 1.97 (50) 24.72 (42)
FR3 DM 1-12 017… 17.5 25.3 0 0 1.97 (50) 1.97 (50) 42.37 (72)
200 Vac to 240
Vac, 50/60 Hz
3-phase
FR1 DM1-321D6… 1.6 2.5 0 0 1.97 (50) 1.97 (50) 14.83 (25.2)
DM1-323D0… 3 4.8 0 0 1.97 (50) 1.97 (50) 14.83 (25.2)
DM1-324D8… 4.8 7.8 0 0 1.97 (50) 1.97 (50) 14.83 (25.2)
DM1-327D8… 7.8 11 0 0 1.97 (50) 1.97 (50) 14.83 (25.2)
FR2 DM1-32011… 11 17.5 0 0 1.97 (50) 1.97 (50) 24.72 (42)
DM1-32017… 17.5 25.3 0 0 1.97 (50) 1.97 (50) 24.72 (42)
FR3 DM1-32025… 25.3 32.2 0 0 1.97 (50) 1.97 (50) 42.37 (72)
FR4 DM1-32032… 32.2 48.3 0 0 1.97 (50) 1.97 (50) 75.56 (128.4)
DM1-32048… 48.3 62.1 0 0 1.97 (50) 1.97 (50) 75.56 (128.4)
A
B
C
D