Chapter 5—Electrical installation
POWERXL SERIES VFDS MN040060EN—September 2020 www.eaton.com
Table 22. International cable and fuse sizes.
IEC cable and fuse sizes
Output rating Input rating IEC application
Input
voltage
Frame
size
Catalog
number
CT/I
H
current
amps
VT/I
L
current
amps
CT/I
H
current
amps
VT/I
L
current
amps
Recom-
mended
fuse
(max.
rating)
100
kAIC
Recom-
mended
miniature
circuit
breaker
(max.
rating)
10/14
kAIC
Recom-
mended
Type E
CMC
(max.
rating)
65 kAIC
Recom-
mended
circuit
breaker
(max.
rating)
100 kAIC
(Open
type only
for
3-phase)
IEC
cable
size
line
and
motor
mm
2
IEC
cable
size
ground
mm
2
Terminal
size
line and
motor
mm
2
Terminal
size
ground
mm
2
100 Vac
to
120 Vac
50/60
Hz
1-phase
FR1 DM1-111D6 1.6 2.5 6.4 10 30 30 \ 30 2.5 2.5 0.2-6 1-6
DM1-113D0 3 4.8 13.5 20 70 63 \ 70 6 6 0.2-6 1-6
FR2 DM1-114D8 4.8 6.9 20 26.4 90 63 \ 90 10 10 0.5-16 1-10
DM1-116D9 6.9 7.8 26.4 30 125 63 \ 125 10 10 0.5-16 1-10
200 Vac
to
240 Vac
50/60
Hz
1-phase
FR1 DM1-121D6 1.6 2.5 4 6.5 15 15 \ 15 2.5 2.5 0.2-6 1-6
DM1-123D0 3 4.8 8 11 30 30 \ 30 2.5 2.5 0.2-6 1-6
DM1-124D8 4.8 7.8 11 17 60 63 \ 60 6 6 0.2-6 1-6
FR2 DM1-127D8 7.8 11 18 23 80 63 \ 80 6 6 0.5-16 1-10
DM1-12011 11 17.5 23 35 125 63 \ 125 10 10 0.5-16 1-10
FR3 DM1-12017 17.5 25.3 38 49.6 200 \ \ 200 16 16 0.5-16 1-16
200 Vac
to
240 Vac
50/60
Hz
3-phase
FR1 DM1-321D6 1.6 2.5 2.1 3.3 6 5 6.3 15 2.5 2.5 0.2-6 1.5-6
DM1-323D0 3 4.8 3.9 5.8 15 10 6.3 15 2.5 2.5 0.2-6 1.5-6
DM1-324D8 4.8 7.8 5.8 9.4 20 15 10 15 2.5 2.5 0.2-6 1.5-6
DM1-327D8 7.8 11 9.4 13.2 30 20 16 20 4 4 0.2-6 1.5-6
FR2 DM1-32011 11 17.5 12.7 20.1 40 30 25 30 6 6 0.5-16 4-10
DM1-32017 17.5 25.3 20.1 29.1 60 40 32 45 10 10 0.5-16 4-10
FR3 DM1-32025 25.3 32.2 29.1 37 70 50 40 50 10 10 0.5-16 6-10
FR4 DM1-32032 32.2 48.3 35.4 5 3.1 100 \ \ 80 25 16 0.5-35 10-16
DM1-32048 48.3 62.1 53.1 68.3 125 \ \ 100 35 16 0.5-35 10-16
380 Vac
to
480 Vac
50/60
Hz
3-phase
FR1 DM1-341D5 1.5 2.2 1.8 2.6 6 4 6.3 15 2.5 2.5 0.2-6 1.5-6
DM1-342D2 2.2 4.3 2.6 5.2 10 8 6.3 15 2.5 2.5 0.2-6 1.5-6
DM1-344D3 4.3 5.6 5.2 6.7 15 10 10 15 2.5 2.5 0.2-6 1.5-6
DM1-345D6 5.6 7.6 6.7 9.1 30 15 10 15 2.5 2.5 0.2-6 1.5-6
FR2 DM1-347D6 7.6 12 9.1 14.4 30 20 16 20 4 4 0.5-16 4-10
DM1-34012 12 16 14.4 19.2 40 25 25 30 6 6 0.5-16 4-10
DM1-34016 16 23 19.2 27.6 60 32 32 40 10 10 0.5-16 4-10
FR3 DM1-34023 23 31 26.5 35.7 70 \ 40 50 10 10 0.5-16 6-10
FR4 DM1-34031 31 38 35.7 43.7 70 \ 50 70 16 16 0.5-35 10-16
DM1-34038 38 46 43.7 52.9 80 \ 58 80 25 16 0.5-35 10-16
525 Vac
to
600 Vac
50/60
Hz
3-phase
FR2 DM1-354D5 4.5 7.5
DM1-357D5 7.5 10
DM1-35010 10 13.5
FR3 DM1-35013 13.5 18
FR4 DM1-35018 18 22
DM1-35022 22 27
Notes:
Line and motor cable size is selected according to IEC 60364-5-52 for copper conductor with PVC insulation with a wiring condition of ambient temperature 30°C
in air and an installation method of “B2” (cables in conduit and cable trunking systems). For other wiring conditions, please refer to the standard of IEC 60364-5-
52:2009 or suitable cable sizes.
Earthing conductor size is determined by the cross-sectional area of phase conductors according to IEC/EN 61800-5-1. So if phase conductor size is changed,
earthing conductor size should also be changed accordingly.
If power cubes or bypass are used, a class gG/gL fuse is recommended.