Chapter 5—Electrical installation
POWERXL SERIES VFDS MN040060EN—September 2020 www.eaton.com
Installation requirements
Figure 8. EMC-compliant setup - 230 Vac, 460/480 Vac, 600 Vac.
2
DM1
otes: N Power cable: L1, L2, L3 and U, V, W.
Control and signal lines: 1 to 24, fieldbus connection large-area connection of all metallic control panel components.
Mounting surfaces of frequency inverter and cable shielding must be free from paint. Connect the cable shielding in
the output of the frequency inverter with a large surface area contact to the ground potential (PES). Large-area cable
shield contacts with motor. Large-area earth connection of all metallic parts.