EasyManua.ls Logo

Eaton SC300 - Serial (RS-232) Communications; GSM Modem Communications

Eaton SC300
166 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
Communications
Copyright © 2007-2018 Eaton Corporation. All Rights Reserved.
IPN 997-00012-03 B2 Issue B2 July 2018
107
Administration of Logon IDs and
Passwords is available in Web. See Web
Access Security on page 117.
7 Click Log On. The SC300 web system page
will be displayed.
8 Click on the appropriate menu item
on the left.
9 To change a setting click the text field,
type the new value, then press Enter
on the PC keyboard. Then click Apply
in the Changes window.
Hold the mouse pointer over any
field for help.
10 Click Log Off (top right of window) to
log out.
Communication via a Network
Management System using SNMP
The SC300 system controller can be configured to allow access by a Network Management
System (NMS), and/or to send alarms as SNMP traps to up to eight different SNMP trap
receivers on an NMS.
To download the SNMP MIB file
This feature is not available in DCTools.
1 In the web view, go to Tools.
2 Right click on SNMP V1/2 SNMP MIB Download.
To allow SNMP access to the SC300
Note: for SNMP V3 access, see To communicate using SNMP V3 on page 108.
1 Set up Ethernet Communications (see details on page 104).
2 On the web, go to System > Interfaces > Remote Access Protocols > SNMP.
3 In DCTools, go to Communications > Remote Access Protocols > SNMP
4 Set the following parameters:
SNMP Access: Disabled: NMS access to the SC300 is not allowed.
All: the NMS has full access to the SC300.
Read Only: the NMS has read only access to the
SC300.
V3 Only: only SNMP v3 access is allowed.
Read Community,
Write Community:
Do not change the default settings unless requested by
the network administrator.

Table of Contents

Related product manuals