SC300 Handbook
56
Copyright © 2007-2018 Eaton Corporation. All Rights Reserved.
IPN 997-00012-03 B2 Issue B2 July 2018
► To view a list of active alarms
• Use the SC300 keypad to go to: Alarms.
• Or, in DCTools/Web, go to System.
Alarm Change Indication
The time and date of the last alarm state change is shown in the web view in Alarm States, Change
column.
Common Alarm Parameters
The following parameters are shared by several, many, or all alarms.
Parameter Description Where to find:
Enable Audible
Alarm Indication
Enable or disable the audible alarm indicator.
SC300: Alarms > Alarm
Settings > Global Settings
DCTools/ Web: Alarms >
Alarm Configuration
Alarm Recognition
Period
All alarms (except those listed below) are
activated only after the alarm condition is
present for this period.
These alarms have individual recognition
periods: AC Fail, System Overload,
Generator Fail.
These alarms do not have recognition periods:
Battery Test Fail, Configuration Error,
Missing Hardware, Standby Mode, String
Fail, Unknown Hardware, Unmapped IOB
Found, and all LVD alarms.