EasyManua.ls Logo

Eaton SC300 - Connector Pin-outs; System Controller Connector Pin-outs

Eaton SC300
166 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
Specifications
Copyright © 2007-2018 Eaton Corporation. All Rights Reserved.
IPN 997-00012-03 B2 Issue B2 July 2018
131
Maximum Cable Length 20m (65 feet)
Connector RJ45
Current Sense Inputs (IOBGP)
Number of Current Sense Inputs 3
Range 50 to +50mV
Resolution <50µV
Accuracy ±0.5% at 25°C [77°F], ±1% over rated temperature
range
Maximum Cable Length 10m (32 feet)
Connector RJ45
Bus Voltage Sense Input (IOBGP)
Number of Bus Voltage Sense Inputs 1
Range 60V to +60V
Resolution 30mV
Accuracy ±0.5% at 25°C [77°F], ±1% over rated temperature
range
Maximum Cable Length 3m (10 feet)
Connector MTA156 (2-way)
Low Voltage Disconnect (IOBGP)
Number of contactor connections
IOBGP-00/ 01
IOBGP-10/11
IOBGP-20/21
2
3
2
Number of LVD channels 16
Contactor Type Normally Open (NO) with auxiliary contacts only.
Contactor Coil Voltage (nominal) 12V, 24V or 48V
Maximum Hold-in Current 1.2A (per contactor)
Maximum Cable Length 3m (10 feet)
Connector MTA156 (4-way)
Power and RXP Comms
Maximum Cable Length (from Voltage Feed
Module)
24V Systems - 100m (325 feet)
48V Systems - 200m (650 feet)
Connector RJ45

Table of Contents