SC300 Operation
Copyright © 2007-2018 Eaton Corporation. All Rights Reserved.
IPN 997-00012-03 B2 Issue B2 July 2018
15
Notes:
1 The parameters available are: Bus Voltage, Rectifier Current, Load Current, Battery Current,
Battery Temperature, Load Power, System Power, Analog Input, Ah Discharged, Energy Meter, Power
Meter, Current Meter, Smart Analog, Alternative Source Current, Solar Power, Generator Power.
2 If Analog Input, Energy Meter, Power Meter, Current Meter, Voltage Meter or Smart Analog is
selected as a display parameter, then also select a value for Value 1/2/3 Index. This value is the
number of the meter or input from the appropriate table.
Display Time-out
If there is no keypad activity for 60 seconds the display will go back to the main screen.
Alarm Indicators
Visual indicators
Power on LED (green)
Minor Alarm LED (yellow)
Critical/Major Alarm LED (red)
???
The system value cannot be displayed because of a failed, disconnected or
unconfigured sensor.
Audible indicator
One beep indicates an invalid key press
Three beeps every 2 seconds refer to the alert message on the display
One beep every 2 seconds Minor alarm is active
Continuous sound Critical/Major alarm is active
Critical/Major alarms always override Minor alarms.
To stop the audible indicator
Press any key
The audible indicator will restart at the next active alarm or alert message.
To enable/disable the audible alarm indicator
Either:
Use the keypad to go to: Alarms > Alarm Settings (tab) > Audible Alarms > Edit.
Or:
In Web go to: System > Interfaces> Physical Ports > Front Panel.
In DCTools, go to Configuration > Communications > Front Panel.
When Disabled, the audible indicator will still indicate an invalid key press.