EasyManua.ls Logo

Eaton SC300 - Communications Security

Eaton SC300
166 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
SC300 Handbook
110
Copyright © 2007-2018 Eaton Corporation. All Rights Reserved.
IPN 997-00012-03 B2 Issue B2 July 2018
Communication via Email
The SC300 system controller can be configured to send Email alarm messages when an alarm
is activated or de-activated.
To set up Email communications:
1 Set up Ethernet communications and connect the SC300 to the IP network. See Ethernet
Communications on page 104.
2 On the web, go to System > Interfaces > Remote Access Protocols > Email Notifications.
3 In DCTools, go to Communications > Remote Access Protocols > Email Notifications.
4 Enable Email Notifications.
5 Set the following parameters:
SMTP Server IP Address
and Port:
The details of the mail server that will be used to send
the Emails.
Return Address: If not blank, any delivery failure notifications will be
sent to this address.
Address Use The setting specifies when the address above is used:
Address only the address appears in the From line
Use Address the return address is shown in the
From line along with other information.
Failure notification onlythe address is only used in
delivery failure notifications.
Subject Prefix: An optional Email subject prefix that will be added to
each Email's subject to allow automatic processing of
the Email.
6 For each Email recipient (up to 6), set the following parameters:
Address: The recipient's Email address.
Level: The severity of alarms that are to be reported to this
recipient.
Select Warnings And Above to send an Email when
an alarm with a severity of Warning or above
changes state.
Select Minor And Above to send an Email when an
alarm with a severity of Minor or above changes
state.
Select Major And Above to send an Email when an
alarm with a severity of Major or above changes
state.
Select None to send no Emails.
Select Critical Only to send an Email when an
alarm with a severity of Critical changes state.
Delay: The alarm Email will be delayed by this length of
time. During this delay, the SC300 will collate all the
events that occur into a single Email.

Table of Contents

Related product manuals